ENGINEERING
SPECIFICATION
|
|
Cable shall
be Alpha Wire Company Alpha Wire INDUSTRIAL
SERIES - SERIES
P Enhanced High
Performance, Stationary Automotive Control Cable.
Manufactured from finely stranded bare copper conductors in accordance
with ASTM-B-3, conductors shall be insulated with a premium grade
of polyvinylchloride/nylon, which meets the flame test requirements
of UL VW-1. Conductor insulation shall comply with UL Standard 62,
Type TFFN, THHN, Oil Res. I & II as well as CSA AWM I A/B FT-4. Red Insulated
conductors shall be numbered with black print for AC circuits
operating at less than line voltage. Blue insulated conductors shall be numbered with white
print for DC circuit applications at less than line voltage. Black insulated conductors shall be numbered with white print for AC circuits operating at less than line voltage.
One green/yellow insulated grounding conductor and one neutral conductor
shall be included and be found in the outermost layer of the core.
The neutral conductor shall be insulated with a white compound and
red stripe for red core cables and a white/blue stripe for blue
core cable designs and a white/black stripe for black core cable designs..
Jackets shall be of a specially formulated, oil and chemical resistant thermoplastic elastomer
complying with the Standards of UL and CSA as well as being compliant
with the requirements of CE-LVD.
Completed cables shall be in compliance with the following certifying
agencies standards:
- UL
Standard 1277, Type TC-ER - 600 Volt
- Standard
13, Type PLTC - 300 Volt, Open Wire
- UL
Standard 13, Open Wire
-
Standard 13, Sunlight Resistant
- UL
Standard 62, Type TFFN - THHN Oil Res. I/II
-
CSA AWM I/II A/B 600 Volt FT-4
-
CE - Low Voltage Directive 73/68/EEC Amendment 93/68/EEC
|
| 1.0 |
PRODUCT
SPECIFICATIONS |
| |
|
| 1.1 |
Finely
stranded bare copper conductor per ASTM-B-3 |
| |
|
| 1.2 |
Conductor
Size: No. 18 AWG through 8 AWG, inclusive |
| |
|
| 1.3 |
Insulation:
Premium grade, lubricated Polyvinylchloride/nylon insulated conductors |
| |
|
| 1.4 |
Color
Code: |
|
| |
Red
insulated conductors with black numbers for AC circuits operating at less than line voltage |
| |
Blue
insulated conductors with white numbers for DC circuits operating at less than line voltage |
| |
Black
insulated conductors with white numbers for AC circuits operating at less than line voltage |
| |
| 1.5 |
Conductor
Styles: |
| |
UL
Type TFFN, THHN |
| |
CSA
AWM I A/B 90°C |
| |
|
| 1.6 |
Cable
Styles: |
|
| |
UL
Type TC-ER |
| |
UL
Type PLTC, Open Wiring |
| |
UL
MTW |
| |
Oil Res. I/II |
| |
UL
Sunlight Resistant |
| |
CSA
AWM I/II A/B 600 Volt FT-4 |
| |
|
| 1.7 |
Jacket: |
|
| |
Premium
Grade, Oil and Chemical Resistant Thermoplastic Elastomer |
| |
Yellow
Color |
| 2.0 |
PERFORMANCE |
| |
|
| 2.1 |
Improved
Cable Life |
| 2.2 |
Reduced
Cable Cost |
| 2.3 |
Oil
Resistant Construction |
| 2.4 |
High
Level of Abrasion Resistance |
| 2.5 |
UL
Listed, CSA Certified, & CE Marked |
| 3.0 |
APPLICATIONS |
| 3.1 |
Stationary
Factory Equipment Interconnections |
| 3.2 |
Stationary
Areas of Industrial Robots |
| 3.3 |
Stationary
Areas of Machine Tools |
| 3.4 |
Stationary
Areas of Automotive Assembly Equipment |
| 3.5 |
Stationary
Areas of Conveyor Systems |
| 3.6 |
Gantry
Crane Stationary Cable |
| 3.7 |
Minimal Flexing Applications |
| 3.8 |
Automated
Storage/Retrieval System Stationary Cable Areas |
| 3.9 |
Stationary
Areas of Automated Dispensing/Packaging Equipment |
| 3.10 |
Automated
Inspection Equipment Stationary Cable Areas |
| 4.0 |
JACKET
TEST DATA |
| |
|
| 4.1 |
| Property |
Test
Method |
Standard |
| Durometer
Hardness |
ASTM
D-2240 |
97/87
|
| Tesile
Strength, psi |
ASTM
D-412 |
2300 |
| Elongation% |
ASTM
D-412 |
300 |
| Oxygen
Index |
ASTM
D-2863 |
30.5 |
| Specific
Gravity |
ASTM
D-792 |
1.44 |
|
|
| |
| |
| |
| |
| |
| |
|
| 4.2 |
Flame
Retardancy |
| |
UL
70,000 Btu Vertical Flame Test |
| |
CSA FT-4 Flame Test |
|